Quick Start
10 ManageUPS
NET
User Instruction Manual
ht=ethernet:ha=002082000179:
gw=198.186.180.1:hd=/tftpboot:
bf=adapter.cfg:vm=rfc1048
This configuration sets the SNMP
adapter interface as follows:
IP address: 198.186.180.63
Subnet mask: 255.255.255.0
Default gateway: 198.186.180.1
Configuration file: /tftpboot/
adapter.cfg
NOTE:
This configuration file is optional. See
Appendix A for more details on the file format.
2. Connect the adapter to the network.
3. The BOOTP server will provide the network
settings to the adapter upon bootup.
4. If a configuration file was specified, then the
adapter will attempt to transfer that file from
a TFTP server residing on the same server as
the BOOTP server. The adapter will
configure itself based on the settings
specified in the configuration file.
5. The adapter can now be configured
remotely using the Web interface, Telnet or
FTP. The default user name is “
admin
”, the
default password is “
admin
”.
Using a Terminal and the Serial Port
To configure the ManageUPS
NET
adapter using
the serial port, follow these instructions:
1. Connect the port
NET
adapter into an ONEAC ON Series
UPS, make sure the DIP switches, located
on the back panel of the UPS are in the
following positions: Dip switch1 is in the
down (OFF) position and DIP switch 2 is in
the up (ON) position.