Buick ManageUPS Manuel d'utilisateur Page 53

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 67
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 52
Appendix D: SNMP MIBS
50 ManageUPSNET User Instruction Manual
upsOutput Group
upsOutputSource Supported values: normal(2), battery(4), booster(5).
upsOutputFrequency Measured average.
upsOutputNumLines Number of phases. This is one for single phase UPS’s.
upsOutputTable
upsOutputVoltage True RMS voltage measurement.
upsOutputCurrent The present output current.
upsOutputPower Represents actual output watts.
upsOutputPercentLoad Values from 0 to about 141% are supported.
upsBypass Group
Not Supported
upsAlarm Group
upsAlarmsPresent The current number of active alarms. After an alarm condition in
the UPS has gone away, it can take up to 1 minute for the alarm to
be removed from the alarm table.
upsAlarmTable
upsAlarmId The instance number of the alarm entry in the alarm table.
upsAlarmDescr The Object Identifier (OID) corresponding to the alarm condition.
upsAlarmTime The value of sysUpTime when the alarm condition occurred.
upsWellKnownAlarms
upsAlarmBatteryBad UPS Battery needs replacing.
upsAlarmOnBattery UPS is running on battery power.
upsAlarmLowBattery Run time left is less than configured low battery alarm value.
upsAlarmDepletedBattery Run time is just about zero.
upsAlarmTempBad Temperature near the battery is too hot.
upsAlarmInputBad Utility power out of limits or not present.
upsAlarmOutputBad Not supported.
upsAlarmOutputOverload Output load power is > 100% of rated capacity.
upsAlarmOnBypass Not applicable.
Table 7. RFC1628 Support (Continued)
Vue de la page 52
1 2 ... 48 49 50 51 52 53 54 55 56 57 58 ... 66 67

Commentaires sur ces manuels

Pas de commentaire